Short title
1. These regulations may be cited as
the Fire Prevention Smoke and
Fire Alarm Regulations.
276/84 s1
Back to Top
Definitions
2. In these regulations
(a) "agency
" means a self?employed person, partnership, corporation,
association or other organization;
(b) "approved
" means acceptable to the fire commissioner;
(c) "dwelling
unit" means a room or suite of rooms operated or intended to be used
as a domicile, by one or more persons and usually containing
cooking, eating, living, sleeping and sanitary facilities;
(d) "owner
" means a person, firm or corporation controlling the property under
consideration;
(e) "referenced
standards" means the latest edition of
(i) National
Standards of Canada
, Standard CAN 4-S 524-M "Standard for the
Installation of Fire Alarm Systems",
(ii) National
Standards of Canada
, Standard CAN 4-S 536 "Standard Testing,
Inspection and Maintenance of existing Fire Alarm Systems",
(iii) National
Standards of Canada
, Standard CAN 4?S 537 (ULC) "Standard for the
Verification of Fire Alarm Systems",
(iv)
Underwriters ' Laboratories of
Canada
(ULC) Standard S-531 "Standard for Smoke Alarms",
(v) Underwriters'
Laboratories of Canada (ULC) Standard S-529 "Smoke Detectors for
Alarm Systems",
(vi) National
Building
Code of Canada
,
(vii) National
Fire Code of Canada
,
(viii) Life
Safety Code National Fire Protection Association No. 101, and
(ix) National
Fire Protection Association "Standard for the Installation,
Maintenance and Use of Household Fire Warning Equipment", N.F.P.A.
No. 74, including appendices A, B and C;
(f) "residential
occupancy" means the occupancy or use of a building or part of it by
persons for whom sleeping accommodation is provided but who are not
harboured or detained to receive medial care or treatment or who are
not involuntarily detained; and
(g) "smoke
alarm" means a combined smoke detector and audible alarm device
designed to sound an alarm within the room or suite in which it is
located upon the detection of smoke within that room or suite.
276/84 s2
Back to Top
Application
3. (1) The installation of approved
smoke alarms applies to
(a)
all new dwelling units constructed as of
the date of these regulations;
(b)
all existing designated sleeping rooms or
areas in the vicinity of sleeping areas;
(c)
residential group C occupancies; and
(d)
others that may be determined by the fire
commissioner.
(2)
Notwithstanding paragraph (1)( b), the
installation of approved smoke alarms does not apply to existing one
or 2 family dwelling units.
276/84 s3
Back to Top
Non-application
4. The installation of smoke alarms
does not apply to
(a)
tents ;
(b)
recreational vehicles;
(c)
newly constructed institutional buildings
as covered by the National Building Code of Canada;
(d)
existing one and 2 family dwelling units,
owner occupied or rented, unless governed by a municipal by-law;
(e)
privately owned and occupied summer
cottages and summer homes; and
(f)
existing institutional occupancies except
as may be determined by the fire commissioner.
276/84 s4
Back to Top
Compliance with codes and
standards
5. The installation, testing and
maintenance of approved smoke alarms shall comply with all
applicable reference codes and standards or those standards that may
be determined by the fire commissioner.
276/84 s5
Back to Top
Requirements
6. (1) The requirements for approved
automatic fire alarm and detection systems in new or existing
buildings shall be as required by the National Building Code of
Canada, or as determined by the fire commissioner for the safety of
the occupants in them.
(2) Fire alarm
systems shall be designed only by competent persons and all
components of fire alarm systems shall be tested, listed and
labelled by a recognized national testing laboratory or as otherwise
approved by the fire commissioner.
(3) The
installation and verification of all newly installed fire alarm and
detection systems and voice communication systems used in
conjunction with fire alarm systems shall comply with all applicable
reference standards, or those standards that may be determined by
the fire commissioner.
(4) The testing
and maintenance of fire alarm and detection systems in buildings,
other than those designated by the National Building Code of Canada
as "high buildings", shall be performed annually, and fire alarm and
detection systems, with and without voice communication in
designated "high buildings", shall be tested and maintained
semi?annually.
(5) Qualified
personnel performing these annual and semi-annual tests and
maintenance referred to in subsection (4) shall follow the
requirements of the National Standards of Canada CAN 4-S 536, and in
the case of "high?rise buildings" the additional requirements as
outlined in the National Fire Code of Canada.
(6) An agency
shall not perform maintenance, repair, inspection, testing or
verification of an installed fire system until, in the opinion of
the fire commissioner, the agency
(a )
has sufficient knowledge of fire alarm systems;
(b)
possesses the necessary testing
equipment; and
(c)
has received a permit to that effect.
(7) A permit
issued under subsection (6) shall remain in force until cancelled,
suspended or surrendered.
(8) A fire alarm
system shall not be temporarily inoperative in an occupied building
required to have a fire alarm system, unless special precautions are
taken by the owners to assure that the occupants can be otherwise
alerted to a fire condition.
(9) Inoperative
fire alarm systems referred to in subsection (8) shall be given high
priority in regard to repairs or adjustments that may be required to
restore them to full operation.
(10) All
emergency powered generating systems for fire alarm systems and
other emergency equipment shall
(a)
be designed to start automatically and
reach full load capacity in approximately 10 seconds after normal
power failure; and
(b)
be tested and maintained in accordance
with the provisions of the National Fire Code of Canada.
(11) Where an
installed sprinkler system functions as a fire detection system or
part of a fire detection system,
(a)
approved manual pull stations shall be
installed by each exit and fire alarm bells on each floor;
(b) both the
manual pull stations and fire alarm bells shall be electrically
connected to the installed fire alarm panel; and
(c)
the operation of one pull station shall
cause the activation of all installed fire alarm bells in the
building.
276/84 s6
Back to Top
Conflict
7. Whenever a conflict exists between
these regulations and a referenced standard, these regulations or
the decision of the fire commissioner shall apply.
276/84 s7
Back to Top
Repeal
8. The Fire Prevention
(Smoke and Fire Alarm) Regulations, 1984, Newfoundland
Regulation 276/84, are repealed.